What the rules require
OSHA requires employers to visually inspect portable extinguishers every month and to have each one maintained once a year (29 CFR 1910.157(e)). You must keep a record of the annual maintenance for one year after the last entry, or for the life of the shell, whichever is less.
Most fire marshals and insurers enforce NFPA 10, which spells out what the monthly inspection covers. The annual maintenance, the 6-year teardown of stored-pressure dry chemical units and the hydrostatic tests are done by a licensed fire equipment company, not by your staff.
How to do the monthly check
- Walk the building with the list of extinguisher locations, so none get skipped.
- At each one, go through the items on the checklist below.
- Initial and date the tag on the extinguisher, or record the check on your phone.
- Take any unit that fails out of service, put a spare in its place and call your service company.
What is due and when
- Monthly: visual inspection by your staff (this checklist).
- Every year: maintenance by a licensed technician, with a new service tag.
- Every 6 years: internal maintenance for stored-pressure dry chemical extinguishers.
- Every 5 or 12 years: hydrostatic test, depending on the extinguisher type.
Fire extinguisher monthly inspection
Monthly, for each extinguisher
Location and access
- In its assigned location
- Nothing blocking access or view
- Location sign or marking visible
- Mounted at the right height, hanger secure
Condition
- Pressure gauge needle in the green
- Full when lifted (no obvious weight loss)
- Safety pin in place and tamper seal intact
- No dents, corrosion, leaks or other damage
- Hose and nozzle not cracked or clogged
- Operating instructions legible and facing out
Records
- Annual service tag present and current
- Monthly inspection initialed and dated
Inspected by, date and notes go at the bottom of the printed sheet.
Run it in Dovient Lite
Add each extinguisher as an asset with its location, print its QR label, and set a monthly schedule with this checklist attached. A work order opens each month; the person doing the round scans the label, marks each item on the phone, and the check is saved on that extinguisher's record with who did it and when.
Start with Dovient LiteSources
- OSHA, Portable fire extinguishers, 29 CFR 1910.157(e)
- NFPA 10, Standard for Portable Fire Extinguishers, Chapter 7, Inspection, Maintenance, and Recharging
Rules change and vary by state and county. Check the current text with your inspector or authority having jurisdiction. Last reviewed 2026-11-15.
Questions
- Who can do the monthly fire extinguisher inspection?
- Any trained employee can do the monthly visual check. The annual maintenance and internal teardowns must be done by a certified fire equipment technician.
- How long do I keep fire extinguisher inspection records?
- OSHA requires the annual maintenance record for one year after the last entry or the life of the shell, whichever is less. Many businesses keep the monthly checks for the same period so they can show them to an inspector.
- Is the tag on the extinguisher enough?
- A dated, initialed tag is accepted as the monthly record in many places. A digital record helps when you have many units, because you can see which ones were missed.