What the rules require
OSHA requires suitable facilities for quick drenching or flushing of the eyes and body within the work area for immediate emergency use, wherever someone's eyes or body may be exposed to injurious corrosive materials (29 CFR 1910.151(c)). Battery acid, many cleaning chemicals and pool chemicals count.
OSHA does not spell out what "suitable" means, and it looks to ANSI/ISEA Z358.1 for that. Z358.1 calls for plumbed eyewash stations to be activated weekly to check that water reaches the heads and to flush the line, and for every station to be inspected once a year against the full standard. It also sets the basics: the station reachable within about 10 seconds, tepid water, and a flush that can run for 15 minutes.
How to do the weekly check
Self-contained stations that are not plumbed cannot be run weekly. Check the fluid level and expiration date weekly, and replace the fluid on the manufacturer's schedule.
- Walk to each station in the order on your list, so none get skipped.
- Check the path is clear and the sign is visible.
- Remove the dust caps and activate the valve; it should open in one motion and stay on without being held.
- Let the water run until it is clear, and check both heads flow evenly.
- Close the valve, replace the caps, and record the check.
Records to keep
Keep a weekly record for each station: date, location, results and who did it, plus the yearly inspection and any repairs. A tag on the station works for the weekly check; a log or digital record shows missed weeks more easily. Neither OSHA nor Z358.1 sets a retention period, so keep at least the last year.
Eyewash station weekly check log
Weekly, for each station
| Date | Station / location | Path clear, sign visible | Water flows to both heads | Water clear, caps replaced | Problem found / action | Initials |
|---|---|---|---|---|---|---|
The printed log has 10 rows per page.
Run it in Dovient Lite
Add each eyewash station as an asset with its location and print a QR label for it. Set a weekly schedule with a checklist of the items above, so a work order opens each week; the person doing the round scans the label, marks each item pass, warning or fail on the phone, and the check is saved on that station's record with who did it and when.
Start with Dovient LiteSources
- OSHA, Medical services and first aid, 29 CFR 1910.151(c)
- ISEA, ANSI/ISEA Z358.1, Emergency Eyewash and Shower Equipment
Rules change and vary by state and county. Check the current text with your inspector or authority having jurisdiction. Last reviewed 2026-11-15.
Questions
- How often should an eyewash station be checked?
- Plumbed stations are activated weekly under ANSI/ISEA Z358.1, and every station gets a full inspection once a year.
- Does OSHA require a weekly eyewash log?
- OSHA requires the eyewash where corrosives are used and looks to ANSI Z358.1 for what is suitable. A weekly record is the simplest way to show the station is maintained.
- How long should the water run during the weekly test?
- Long enough to show water reaches both heads and to clear out the line. Many sites run it until the water is clear, often a few minutes.
- What about portable eyewash stations?
- Check the fluid level and expiration date weekly, and replace the fluid on the manufacturer's schedule.