What the rule requires
Since October 13, 2018, owners and operators of underground storage tank systems must do periodic walkthrough inspections (40 CFR 280.36). You can follow the federal list, a code of practice such as PEI RP900, or a checklist written by your state UST program. Many states run their own UST program under EPA approval, and some add items, so check your state's form first.
- Every 30 days: spill prevention equipment (spill buckets) and release detection equipment. If deliveries come less often than every 30 days, spill buckets may be checked before each delivery instead.
- Once a year: containment sumps and handheld release detection equipment, such as tank gauge sticks and groundwater bailers.
What each check covers
- Spill buckets: look for damage, remove any liquid or debris, check the fill pipe for obstructions, make sure the fill cap is on tight, and check the interstitial space on double-walled buckets for a leak.
- Release detection: make sure the tank gauge or monitoring system is on, with no alarms or unusual conditions, and that the release detection records are reviewed and current.
- Containment sumps (yearly): look for damage, leaks into the sump or releases to the environment, remove liquid or debris, and check the interstitial space on double-walled sumps.
- Handheld equipment (yearly): gauge sticks readable and not worn, bailers working.
Records to keep
Keep walkthrough records for one year (280.36(b)), at the site or where they can be provided to the inspector on request (280.34(c)). Each record must list every area checked, whether it was acceptable or needed action, what was done to fix any problem, and delivery records if spill buckets are checked less often than every 30 days.
The walkthrough is separate from the testing in 280.35, where spill buckets are tested and overfill equipment inspected at least every three years. A state inspector usually asks for the walkthrough records, the release detection records and the latest three-year test results together.
UST walkthrough inspection
Every 30 days, with annual items once a year
Spill buckets, every 30 days
- Spill bucket not cracked or damaged
- Spill bucket empty, no liquid or debris
- Fill pipe clear of obstructions
- Fill cap on and secure
- Double-walled bucket interstice shows no leak
Release detection, every 30 days
- Tank gauge or monitor on and working
- No alarms or unusual conditions on the console
- Release detection records reviewed and current
Containment sumps, yearly
- Sump not cracked or damaged
- No liquid, debris or product in the sump
- No sign of a release to the environment
- Double-walled sump interstice shows no leak
Handheld equipment, yearly
- Tank gauge stick readable and not worn
- Groundwater bailer working
Inspected by, date and notes go at the bottom of the printed sheet.
Run it in Dovient Lite
Add each tank system as an asset and print a QR label for the office. Set a monthly schedule with the 30-day items and a yearly schedule with the sump and handheld items; a work order opens when each is due. The clerk or Class B operator marks each item on the phone with a photo of anything that needs action, the record stays on the tank's history with who did it and when, and completed walkthroughs export as a PDF for the state inspector.
Start with Dovient LiteSources
- EPA, Periodic operation and maintenance walkthrough inspections, 40 CFR 280.36
- EPA, Reporting and recordkeeping, 40 CFR 280.34
- EPA, Operating and maintaining UST systems: practical help and checklists
Rules change and vary by state and county. Check the current text with your inspector or authority having jurisdiction. Last reviewed 2026-11-15.
Questions
- How often is a UST walkthrough inspection required?
- Every 30 days for spill buckets and release detection equipment, and once a year for containment sumps and handheld release detection equipment.
- How long do I keep UST walkthrough records?
- One year. Keep them at the site or somewhere you can produce them for the inspector on request.
- Can I use my state's walkthrough form instead of EPA's list?
- Yes. The rule allows a checklist developed by the implementing agency or a code of practice such as PEI RP900, as long as it covers comparable equipment.
- Who can do the monthly UST inspection?
- The federal rule does not name a person. Usually it is a trained Class B operator or a clerk the Class B operator has trained.