Who checks what
Three groups touch your dispensers. Store staff do a quick look every day. Your fuel equipment contractor services filters, hoses, nozzles and meters and does calibration. State or local weights and measures officials test the meters with a certified 5-gallon prover and put a dated seal or sticker on the pump when it passes. Separately, the EPA underground storage tank rules cover the leak detection and containment under and around the dispenser.
Daily fuel pump inspection
- Hoses not kinked, cracked, flattened or leaking. Breakaway couplings connected.
- Nozzles not leaking, hold-open clips and boots intact, and nozzles shut off when the tank fills.
- Display and price readable on every side, and the price matches the sign.
- No fuel on the island or dripping inside the dispenser cabinet.
- Card readers not tampered with: seals or tape on the door intact, no extra devices on the bezel.
- Emergency stop button visible and labeled, and island clear of trash.
Gas pump maintenance schedule
- Weekly: open each dispenser door (or check the sump) for drips, and test that nozzles shut off.
- Monthly or when flow slows: check flow rate. A drop often means a plugged dispenser filter.
- Dispenser filters: replace at the interval your contractor or the filter maker sets, and whenever flow drops.
- Hoses, nozzles and breakaways: replace when worn, and after any drive-off.
- Under-dispenser containment sumps: keep dry and clear of debris; the EPA rule calls for an annual check of containment sumps used for interstitial monitoring.
- Line leak detectors: tested for operation at least once a year by simulating a leak (40 CFR 280.40(a)(3)).
- Calibration: after a meter repair or replacement, and when your own 5-gallon test can shows the meter drifting.
Fuel dispenser calibration and tolerances
NIST Handbook 44, which states adopt for weights and measures, sets how accurate a retail motor fuel dispenser must be. For a pump in use, the maintenance tolerance on a 5-gallon test is plus or minus 6 cubic inches. A newly installed or repaired pump must meet the tighter acceptance tolerance, half that, plus or minus 3 cubic inches.
A pump that is out of tolerance can be ordered out of service by the inspector until it is repaired and recalibrated. Inspection frequency and fees are set by each state, so ask your state weights and measures office.
What to record
Keep a record per dispenser: daily checks, filter changes with the date, hose and nozzle replacements, calibration results before and after adjustment, and each weights and measures inspection result. Keep line leak detector and sump test results for the period your state and the EPA rules require. The history shows which dispensers fail most and backs you up when an inspector or customer questions a meter.
Run it in Dovient Lite
Add each dispenser as an asset with a QR label on the cabinet, and set a daily checklist plus monthly and yearly schedules for filters, leak detector tests and calibration. Staff mark each item pass, warning or fail on the phone with photos, and can report a leaking nozzle as a breakdown that notifies the assigned people. Parts like filters, hoses and nozzles come off stock when used, and completed work orders export as PDF.
Start with Dovient LiteSources
- NIST Office of Weights and Measures, Gasoline dispensers
- NIST Handbook 44, current edition, Section 3.30 Liquid-Measuring Devices
- eCFR, UST release detection: general requirements, 40 CFR 280.40
- EPA, Underground Storage Tanks
Rules change and vary by state and county. Check the current text with your inspector or authority having jurisdiction. Last reviewed 2026-11-15.
Questions
- How often are gas pumps inspected?
- Store staff should look them over daily. State or local weights and measures officials test meters on a schedule each state sets, and also after customer complaints.
- What is the allowed error on a gas pump?
- Under NIST Handbook 44, a pump in service may be off by up to 6 cubic inches on a 5-gallon test. A newly installed or repaired pump must be within 3 cubic inches.
- How often should dispenser filters be changed?
- At the interval your fuel equipment contractor or filter maker sets, and sooner when flow rate drops. A slow pump is usually a plugged filter.
- Do line leak detectors need testing?
- Yes. Federal UST rules require an annual operation test of automatic line leak detectors, done by simulating a leak (40 CFR 280.40(a)(3)). Your state may set more.