Where the rules come from
The federal pretreatment rules (40 CFR 403.5(b)(3)) ban discharging solid or viscous pollutants that obstruct flow in the public sewer. Fats, oils and grease (FOG) from kitchens are the classic case. EPA leaves the details to the local sewer authority, so your city or sanitary district sets the actual rules through a FOG ordinance or your sewer permit.
EPA's guidance says interceptors must be sized to let grease cool and separate, and serviced at regular intervals. The frequency depends on how much grease you make and the kitchen practices you follow.
What most city FOG programs require
Rules differ by city, so read your own ordinance or ask your FOG inspector. The common pattern looks like this:
- Pump and clean the interceptor when grease and solids reach 25% of its depth, or at a set interval such as every 90 days, whichever comes first. San José and Santa Clara, California, use this rule.
- Small under-sink grease traps are cleaned more often, weekly or every two weeks in many cities, by staff or a contractor.
- Use a permitted grease hauler and keep the hauler's manifest or receipt for each pump-out.
- Keep the cleaning records on site, commonly for three years, and show them on request.
- Follow kitchen best practices: scrape plates into the trash, no grease down sinks, use drain screens.
What the grease trap inspection looks at
- The maintenance log and hauler receipts, with no gaps longer than the required interval.
- Grease and solids depth in the trap at the time of the visit.
- Baffles, tees and lids in place and not broken.
- Signs of enzymes or additives that some cities ban because they only move grease downstream.
- Kitchen practices: drain screens, no grease poured down sinks, staff training.
How to use the log
- Measure the grease and solids layer on a set day each week for small traps, or at each service for large interceptors.
- Write down the date, the depth or percent full, and what was done.
- When a hauler pumps the interceptor, record the company, the gallons removed and the manifest number, and staple the receipt to the log.
- Note any damage, odors or slow drains, and get them repaired.
Grease trap and interceptor maintenance log
Each cleaning, pump-out or inspection
| Date | Trap or interceptor | Grease and solids (% full) | Work done (cleaned, pumped, inspected) | Hauler and manifest no. | Gallons removed | Condition notes | Initials |
|---|---|---|---|---|---|---|---|
The printed log has 10 rows per page.
Run it in Dovient Lite
Add each grease trap and interceptor as an asset and set a schedule for its cleaning interval, weekly for small traps or every 90 days for an interceptor, with a short checklist for baffles, lid and drain screens. The work order opens when it is due; note the percent full, gallons and manifest number in its comments and attach a photo of the hauler's receipt. Completed work orders export as PDF for the FOG inspector.
Start with Dovient LiteSources
- EPA, General pretreatment regulations: prohibited discharges, 40 CFR 403.5(b)(3)
- EPA, Controlling fats, oils, and grease discharges from food service establishments, EPA-833-F-12-003
- City of San José, Grease interceptor maintenance guidance
Rules change and vary by state and county. Check the current text with your inspector or authority having jurisdiction. Last reviewed 2026-11-15.
Questions
- How often should a restaurant grease trap be cleaned?
- Your city sets the rule. A common one is to pump the interceptor when it is 25% full of grease and solids or every 90 days, whichever comes first. Small under-sink traps are often cleaned every week or two.
- What records do I need for grease trap maintenance?
- A log of each cleaning and inspection with the date and how full it was, plus the hauler's manifest or receipt for each pump-out. Many cities ask you to keep them on site for three years.
- Is there a federal grease trap law?
- Only indirectly. The federal pretreatment rules ban discharges that block the sewer, and local sewer authorities enforce that with their own FOG ordinances and permits.
- Who inspects grease traps?
- Usually the city or sanitary district's FOG or pretreatment inspector. Some health departments also look at the grease trap log during routine inspections.