Which codes apply to an ASC
Medicare's Conditions for Coverage require an ASC to meet the 2012 Life Safety Code (NFPA 101) for ambulatory health care occupancies, no matter how many patients it serves (42 CFR 416.44(b)). They also require the 2012 Health Care Facilities Code, NFPA 99, except chapters 7, 8, 12 and 13 (416.44(c)). State surveyors and accrediting bodies such as AAAHC and The Joint Commission check against these, using the K-tags (life safety) and E-tags (emergency preparedness) in CMS's survey forms.
NFPA 99 covers the building systems that keep patients safe: medical gas and vacuum (chapter 5), electrical systems including the essential electrical system and generator (chapter 6), and patient care electrical equipment (chapter 10). For generator testing it points to NFPA 110. The Life Safety Code points to NFPA 25 for sprinklers, NFPA 72 for fire alarms and NFPA 10 for extinguishers.
Tests and how often
- Generator: inspected weekly, and run monthly for at least 30 minutes under load (NFPA 110). Level 1 systems also get a 4-hour load test at least every 36 months.
- Transfer switches: operated monthly with the generator test.
- Emergency lighting: 30-second test every month and a 90-minute test once a year (NFPA 101, 7.9.3).
- Fire extinguishers: visual check monthly, maintenance yearly (NFPA 10).
- Fire drills: once per shift per quarter, with a written record.
- Sprinklers, fire alarm and smoke dampers: inspected and tested by licensed contractors at the NFPA 25, 72 and 80/105 intervals.
- Medical gas and vacuum: inspected and maintained under NFPA 99 chapter 5, including alarms and zone valves.
- Emergency plan: reviewed at least every 2 years, with exercises at least once a year (42 CFR 416.54).
How to stay compliant
- List every life safety system and device: generator, transfer switches, exit and emergency lights, extinguishers, fire doors, medical gas alarms.
- Set each test at its code interval and assign it to a person or contractor.
- Do environment of care rounds monthly or on your accreditor's schedule, looking for blocked exits, propped fire doors, stored items in corridors and damaged ceiling tiles.
- Fix what you find, and record the date and who fixed it.
- Before a survey, pull the last 12 months of every test and check nothing is missing.
What a surveyor looks at
The surveyor asks for the generator testing log, emergency light and extinguisher records, fire drill reports, and contractor reports for sprinklers, fire alarm and medical gas. They walk the building to check exits, fire doors, the generator and medical gas alarm panels. Missing months in a log are the most common finding, so a record for every scheduled test matters more than anything else.
Run it in Dovient Lite
Add the generator, transfer switches, emergency lights, extinguishers and medical gas alarms as assets, and set each test as a schedule at its code interval with a checklist attached. A work order opens when each test is due, and the person doing it marks each item pass, warning or fail on the phone; contractor reports are attached to their work orders. Before a survey, export the completed tests as a PDF with dates and who did each one.
Start with Dovient LiteSources
- CMS, Condition for coverage: Environment, 42 CFR 416.44
- CMS, Emergency preparedness, 42 CFR 416.54
- NFPA 99, Health Care Facilities Code
- NFPA 110, Emergency and Standby Power Systems
Rules change and vary by state and county. Check the current text with your inspector or authority having jurisdiction. Last reviewed 2026-11-15.
Questions
- What is NFPA 99 in simple terms?
- It is the Health Care Facilities Code. It sets how medical gas, electrical systems, generators and patient care equipment in health care buildings are installed, tested and maintained. CMS requires ASCs to follow the 2012 edition.
- How often does an ASC have to test its generator?
- Under NFPA 110, inspect it weekly and run it under load for at least 30 minutes each month. Level 1 systems also need a 4-hour load test at least every 36 months.
- How often are fire drills required in a surgery center?
- Once per shift each quarter under the Life Safety Code for ambulatory health care, with a written report of each drill. Your state may add to this.
- What records does a surveyor ask for?
- Generator logs, emergency light and extinguisher checks, fire drill reports, and contractor reports for sprinklers, fire alarm and medical gas. Expect them to check that every month and quarter is there.