Glycol system maintenance
The glycol chiller holds fermentation temperatures for every tank in the cellar. When it fails on a hot day, fermentations run warm and a batch can be lost in hours. Most chiller failures trace back to a dirty condenser, low or diluted glycol, or a pump that was not checked.
- Daily: check the glycol supply temperature and reservoir level; listen to the pump and compressor; look for leaks at fittings and tank jackets.
- Monthly: check glycol concentration with a refractometer and top up with premixed glycol, not water; clean the condenser coils on air-cooled units, more often in dusty or hot seasons; check pump seals and strainers.
- Quarterly: inspect insulation on supply and return lines, check solenoid valves and controllers on each tank, check the electrical connections for heat.
- Yearly, before summer: service by a refrigeration technician, including refrigerant charge, pressures, contactors and fans.
Brewhouse and cellar
Take every interval from the equipment manuals and adjust with your own history. Keep spare pump seals, gaskets and solenoid valves on the shelf.
- Each brew: check valves, gaskets and sight glasses; inspect the heat exchanger outlet temperature against your target.
- Weekly: inspect pump seals and impellers on the wort and transfer pumps; clean the hop back or whirlpool screens; check the mash rake or mixer drive for noise.
- Monthly: open and inspect the plate heat exchanger on a schedule your water and process call for, or when temperatures drift; grease motor bearings per the manual; inspect tank pressure relief and vacuum relief valves.
- Yearly: boiler or steam generator inspection as your state requires; gearbox oil changes on the mash rake and mill; calibration of thermometers and pressure gauges.
Brewery regulations that touch maintenance
- FDA: beer is a food. Breweries that hold a TTB permit and are registered with FDA are exempt from the preventive controls rules in Subparts C and G of 21 CFR Part 117 for their alcoholic beverages (117.5(i)), but the current good manufacturing practice rules in Subpart B still apply, including keeping plant and equipment cleanable and in good repair (117.35 and 117.40).
- OSHA: tanks are permit-required confined spaces if they meet the definition in 29 CFR 1910.146, and carbon dioxide from fermentation is a hazard in cellars. Lock out pumps, mixers and the mill before working on them (1910.147).
- State and local: boiler and pressure vessel inspections, and state alcohol regulators. Rules such as New Jersey's differ, so check your state agency.
Glycol chiller monthly check
Monthly
Glycol
- Reservoir level at the full mark
- Glycol concentration within your target
- Supply temperature holding at set point
- No leaks at fittings, valves or tank jackets
Chiller
- Condenser coils clean
- Compressor runs with no unusual noise
- Fans spin freely and blades not damaged
- No ice buildup on lines or evaporator
Pumps and lines
- Pump seals dry, no leaks
- Strainer clean
- Line insulation intact, no condensation
- Tank solenoid valves open and close on call
Inspected by, date and notes go at the bottom of the printed sheet.
Run it in Dovient Lite
Add the glycol chiller, pumps, heat exchanger, mash tun, kettle and each fermenter as assets, and set preventive schedules by date, such as the monthly chiller check with this checklist and the yearly service before summer. The brewer marks each item pass, warning or fail on the phone with a photo, and the record stays on the equipment. Keep pump seals and gaskets in the parts list with a minimum quantity, so items below it show as low stock.
Start with Dovient LiteSources
- FDA, Current good manufacturing practice and preventive controls for human food: exemptions, 21 CFR 117.5(i)
- FDA, Equipment and utensils, 21 CFR 117.40
- OSHA, Permit-required confined spaces, 29 CFR 1910.146
Rules change and vary by state and county. Check the current text with your inspector or authority having jurisdiction. Last reviewed 2026-11-15.
Questions
- How often should a glycol chiller be serviced?
- Check temperatures and levels daily, check glycol concentration and clean the condenser monthly, and have a refrigeration technician service it once a year before summer.
- Can I top up a glycol system with water?
- Only if you then bring the concentration back to your target. Topping up with water alone dilutes the glycol and raises its freezing point, which can freeze lines and jackets.
- Does FDA regulate breweries?
- Yes. Beer is a food under federal law. TTB-permitted breweries are exempt from the preventive controls rules for their beer, but must follow FDA's current good manufacturing practices.
- What is a good maintenance schedule for a brewery?
- Daily chiller and cellar checks, weekly pump and screen checks, monthly glycol and heat exchanger work, and yearly technician service of the chiller and boiler, with intervals taken from each manual.