TL;DR
If the motor trips on start, megger the windings to ground. Above 100 MΩ is healthy; below 1 MΩ means a winding-to-ground fault and the motor needs to be rewound or replaced.
What you might see
- breaker trips immediately on start
- motor hums but doesn't rotate
- ground fault indicator lit
- overload relay trips at zero current
Likely causes
Winding-to-ground insulation breakdown from heat aging or moisture ingress
Phase-to-phase winding short
Open winding, broken conductor or burned termination
Faulty contactor or starter (not the motor itself)
Required tools
- Megohmmeter (500V or 1000V test voltage)
- Multimeter
- Grounding stick or shorting jumper
- LOTO kit
Safety first
- A megger applies hundreds of volts DC. Always discharge windings to ground after a test before touching the leads.
- NEVER megger a motor while it is connected to a VFD. Disconnect the VFD output cables first.
- Lock out the motor disconnect before starting any winding test.
Procedure
- 1
Lock out and tag out the upstream disconnect.
- 2
Disconnect the motor leads from the contactor or VFD output terminals.
Warning: If the motor is connected to a VFD, you MUST disconnect the VFD output before applying a megger. Megger DC voltage will destroy the VFD output stage. - 3
Set the megohmmeter to 500V test voltage.
- 4
Connect one lead to motor lead T1, the other to the motor frame or ground. Apply test for 60 seconds and read the resistance.[1]
- 5
Healthy reading is greater than 100 MΩ. Between 10 and 100 MΩ is degraded but operable. Below 1 MΩ indicates a winding-to-ground fault.[1]
- 6
Repeat the test on T2 and T3 motor leads.
- 7
Discharge each winding to ground with a grounding stick before disconnecting the megger.
- 8
Test winding-to-winding resistance with a multimeter on the lowest ohms range. The three phase readings should be within 5% of each other.
- 9
If any test fails, the motor cannot be repaired in the field. Tag it Out of Service and send it to a qualified motor rewind shop, or order a replacement.
- 10
If the windings test healthy, look upstream, check the contactor coil and contacts, the overload relay, and the incoming voltage.
Sources
Baldor Reliance Industrial Motor Maintenance Manual, Baldor Electric Company (ABB)
Baldor Industrial Motor Maintenance Manual, insulation resistance test procedure (general)
View source
More guides for Baldor Super-E (EM/EJMM)
How to diagnose bearing noise and vibration on a Baldor Super-E motor
Vibration is most often a worn bearing. Listen for grinding, log a vibration reading, and plan a bearing replacement during the next planned outage.
How to diagnose intermittent operation on a Baldor Super-E motor
Intermittent stops or restarts almost always come from loose electrical connections or a worn contactor. Check the contactor first, then torque-test the conduit box terminals.
How to fix a Baldor Super-E motor making noise from coupling misalignment
Misalignment between the motor and the driven equipment creates a knocking or rumbling noise. Check soft foot first, then measure parallel and angular alignment with a dial indicator or laser tool.
How to fix overheating and excessive current draw on a Baldor Super-E motor
Overheating with high current is usually mechanical overload or supply phase imbalance. Measure phase currents, check the load, and verify supply voltage balance is within 1%.
Related learning guides
Stop fixing the same fault twice.
Dovient turns guides like this into your team's shared playbook, with AI that catches recurring issues before they break the line.