TL;DR
Insulation degradation in an MCC is confirmed by a megohmmeter test. Test bus-to-ground and each bucket's wiring. Any reading below 10 megohms requires investigation before the equipment is returned to service.
What you might see
- ground fault indicator alarm active
- visual surface tracking or carbonized residue on bus insulation
- condensation or dust coating visible inside the MCC
- periodic nuisance trips correlated with humid weather
Likely causes
Moisture ingress from condensation or water entry through enclosure penetrations
Accumulated conductive dust (carbon, metallic, or chemical) bridging insulation surfaces
Age-related cracking or chalking of molded bus insulation
Prior over-voltage transient or fault arc scarring the bus insulation
Required tools
- Megohmmeter (1000V test voltage)
- True-RMS multimeter for zero-voltage verification
- Dry lint-free cloths
- Arc-flash PPE
- LOTO kit with grounds
Safety first
- A megger applies up to 1000V DC. Discharge all bus sections to ground with a grounding stick after each test before touching terminals.
- Confirm zero voltage on the bus with a meter before connecting the megger. Never megger a live bus.
Procedure
- 1
De-energize the MCC fully: open the incoming feeder breaker, lock out the feeder, and verify zero voltage at the main bus with a meter.
Warning: A full MCC de-energization typically requires utility coordination if the incoming feed is from a medium-voltage transformer. Follow your facility's switching permit procedure. - 2
Disconnect all motor leads from the starter buckets to prevent measuring motor winding insulation instead of MCC insulation.[1]
- 3
Set the megohmmeter to 1000V test voltage for a 480V MCC.
- 4
Test each bus phase to ground: connect the positive megger lead to the bus and the negative lead to the MCC chassis ground. Apply for 60 seconds and record the reading.[1]
- 5
Healthy bus insulation reads above 100 megohms. Between 10 and 100 megohms is degraded but operable. Below 10 megohms requires investigation and repair before re-energization.
- 6
For sections with low readings, inspect the bus insulation visually for cracks, tracking, or contamination. Clean contaminated surfaces with a dry, lint-free cloth. Do not use solvent-based cleaners on molded bus insulation.
- 7
Replace any bus section with cracked, tracking, or physically damaged insulation before re-energizing.
- 8
Re-test after cleaning and repairs. Record all readings in the MCC maintenance log.
Sources
Square D Model 6 Motor Control Center Instruction Bulletin, Square D (Schneider Electric)
Square D Model 6 MCC installation and maintenance instructions, insulation resistance test procedures and acceptance criteria (general)
View source
More guides for Square D (Schneider Electric) Model 6 MCC
How to respond to arc flash signs and pitting inside a Square D Model 6 MCC
Evidence of prior arcing inside an MCC means the equipment is unsafe until fully inspected and repaired. De-energize, assess the damage, replace any component with arc pitting or carbon tracking, and perform a root-cause review before re-energizing.
How to diagnose a circuit breaker that fails to close in a Square D Model 6 MCC
A breaker that won't close usually has a discharged spring or a coil fault. Check the spring charge indicator, test the closing coil voltage, and replace the coil or the breaker if the mechanism is damaged.
How to find and fix hot spots on busbars in a Square D Model 6 MCC
Hot spots on MCC busbars are caused by loose bolted connections or sustained overload. Scan with a thermal camera, de-energize, re-torque, and re-scan under load to verify the repair.
How to fix nuisance tripping from a faulty trip unit in a Square D Model 6 MCC
Nuisance trips with measured current well below the trip setting point to a trip unit fault or CT calibration drift. Verify with a secondary injection test and replace the trip unit if it fails.
Related learning guides
Pump Failure: 8 Common Causes
The most frequent pump failure modes and how to prevent them.
Read guideMotor Troubleshooting: Symptoms to Fix
Read motor symptoms correctly and get to the root cause in minutes, not hours.
Read guideLubrication Best Practices
The most overlooked maintenance task, and how to do it right.
Read guideStop fixing the same fault twice.
Dovient turns guides like this into your team's shared playbook, with AI that catches recurring issues before they break the line.