TL;DR
Hot spots on MCC busbars are caused by loose bolted connections or sustained overload. Scan with a thermal camera, de-energize, re-torque, and re-scan under load to verify the repair.
What you might see
- thermal camera shows hot spot at a busbar joint or section
- IR thermometer reading above 60 degrees Celsius on the bus
- discoloration or oxidation at a busbar bolted joint
- downstream breaker tripping without overcurrent cause
Likely causes
Loose bolted joint at a busbar splice, tap, or stab reducing contact area and increasing resistance
Chronic overload on a section of the bus carrying current above its ampacity rating
Oxidized contact surface at a bolted joint, especially on aluminum bus
Missing or corroded Belleville washer reducing clamping force
Required tools
- Thermal camera
- Torque wrench (calibrated to bus bolt spec)
- No-oxide compound (for aluminum bus)
- Fine emery cloth or wire brush
- Arc-flash PPE rated for the MCC's incident energy
- LOTO kit with grounds
Safety first
- All thermal scanning inside an energized MCC requires arc-flash PPE and an energized electrical work permit. Do not reach into the bus section.
- Apply LOTO and verify de-energization before touching any busbar or bolted connection. MCCs contain multiple energy sources.
Procedure
- 1
With the MCC energized and under load, open only the front door panel for the section to be inspected. Do NOT enter the rear or pull out a bucket.
- 2
Perform a thermal scan of all visible busbar sections and joints using a thermal camera. Note the temperature of each joint relative to the bus average.
Warning: This is energized work. Wear arc-flash PPE rated for the MCC's incident energy. An energized electrical work permit is required. - 3
Flag any joint that is more than 15 degrees Celsius above the ambient bus temperature as a hot spot requiring attention.[1]
- 4
Coordinate a controlled de-energization: open the main incoming breaker, lock out both the incoming feeder and the main breaker, and apply grounds if required by your facility procedure.
Warning: MCCs contain live conductors above and below the main breaker even when the main is open. Follow your facility's arc-flash and energy isolation procedure exactly. - 5
Remove the dead-front covers of the affected section.
- 6
Inspect the hot-spot joint: check the bolt for looseness, inspect the contact faces for oxidation or contamination, and verify the Belleville washer is present and oriented correctly.[1]
- 7
Clean the contact faces with fine emery cloth or a wire brush and apply no-oxide compound if bus is aluminum. Re-torque the joint bolt to the value in the Square D Model 6 bus connection instructions.
- 8
Re-install dead-front covers, restore power, and re-scan with the thermal camera after 15 minutes at full load. Temperature should now match the rest of the bus.
Sources
Square D Model 6 Motor Control Center Instruction Bulletin, Square D (Schneider Electric)
Square D Model 6 Motor Control Center installation and maintenance instructions, busbar connection torque and inspection procedures (general)
View source
More guides for Square D (Schneider Electric) Model 6 MCC
How to respond to arc flash signs and pitting inside a Square D Model 6 MCC
Evidence of prior arcing inside an MCC means the equipment is unsafe until fully inspected and repaired. De-energize, assess the damage, replace any component with arc pitting or carbon tracking, and perform a root-cause review before re-energizing.
How to diagnose a circuit breaker that fails to close in a Square D Model 6 MCC
A breaker that won't close usually has a discharged spring or a coil fault. Check the spring charge indicator, test the closing coil voltage, and replace the coil or the breaker if the mechanism is damaged.
How to assess insulation degradation in a Square D Model 6 MCC
Insulation degradation in an MCC is confirmed by a megohmmeter test. Test bus-to-ground and each bucket's wiring. Any reading below 10 megohms requires investigation before the equipment is returned to service.
How to fix nuisance tripping from a faulty trip unit in a Square D Model 6 MCC
Nuisance trips with measured current well below the trip setting point to a trip unit fault or CT calibration drift. Verify with a secondary injection test and replace the trip unit if it fails.
Related learning guides
Equipment Breakdown Response
The step-by-step playbook for the first 15 minutes after a critical machine goes down.
Read guideHydraulic System Troubleshooting
Diagnose the most common hydraulic failures, fast.
Read guideElectrical Fault Finding
Step-by-step electrical fault diagnosis for plant technicians.
Read guideStop fixing the same fault twice.
Dovient turns guides like this into your team's shared playbook, with AI that catches recurring issues before they break the line.