TL;DR
The CompactLogix 5380 battery alarm is straightforward: order the correct lithium battery, replace it with the controller powered on to preserve memory, and acknowledge the alarm. The battery typically lasts 5 to 7 years.
What you might see
- battery LED on the controller face flashing amber
- Studio 5000 controller properties shows battery low status
- battery low fault in the controller fault log
- battery has not been replaced in more than 5 years
Likely causes
Lithium backup battery reaching end-of-life after 5 to 7 years of service
Controller power cycled frequently, increasing battery drain from unplanned power-off events
High ambient temperature accelerating battery self-discharge
Required tools
- Replacement lithium battery (Rockwell-approved catalog number for 5380)
- Small flathead screwdriver (for battery door if required)
Safety first
- Replace the battery with the controller powered on. Replacing with power off risks program loss if no backup SD card is in place.
- Do not short-circuit or incinerate the lithium battery. Dispose of it as hazardous waste per your facility's procedure.
Procedure
- 1
Order the replacement battery by the Rockwell catalog number shown on the existing battery or in the CompactLogix 5380 User Manual. Do not substitute a generic battery.[1]
- 2
Confirm the controller is powered on before replacing the battery. Replacing the battery with power off will erase the program if no SD card or nonvolatile memory backup exists.[1]
- 3
Open the controller battery door on the front of the controller module. The door is typically a small hinged cover on the bottom-left of the module face.
- 4
Note the polarity of the existing battery before removing it.
- 5
Remove the old battery and immediately insert the new battery with correct polarity. Do not leave the battery socket empty for more than 30 seconds while the controller is powered.[1]
- 6
Close the battery door.
- 7
Confirm in Studio 5000 (Controller Properties, General tab) that the battery status has cleared. The amber LED should go out within a few minutes.
- 8
Dispose of the old lithium battery per your facility hazardous waste procedure.
Sources
Allen-Bradley CompactLogix 5380 Controllers User Manual (Pub 5069-UM001), Rockwell Automation (Allen-Bradley)
Allen-Bradley CompactLogix 5380 Controllers User Manual, battery replacement procedure and part number (general)
View source
More guides for Allen-Bradley (Rockwell) CompactLogix 5380
How to fix EtherNet/IP communication errors on an AB CompactLogix 5380
EtherNet/IP communication errors on a CompactLogix 5380 start with physical layer checks: cable, switch port, and IP address. Then check the Studio 5000 connection configuration for timeout and RPI settings.
How to replace a failed I/O module on an AB CompactLogix 5380 PLC
A failed I/O module shows a red fault LED and logs a fault code in Studio 5000. Note the slot number and module catalog number, go online with the PLC, inhibit the module, swap it, and re-enable it without modifying the program.
How to recover from program corruption on an AB CompactLogix 5380
Program corruption shows as a major fault on power-up or a checksum error in the fault log. Restore from the latest validated ACD backup in Studio 5000 or from the SD card if auto-restore was configured.
How to diagnose sensor reading drift on an AB CompactLogix 5380 analog input
Analog input drift is usually wiring noise or a loose field terminal. Measure the sensor signal directly at the field terminal and compare to the PLC tag value. If they differ, the I/O module or scaling is the issue. If the signal itself is noisy, fix the cable shielding.
Related learning guides
Electrical Fault Finding
Step-by-step electrical fault diagnosis for plant technicians.
Read guideVibration Analysis Basics
What your equipment is telling you before it fails.
Read guideBearing Replacement: When, Why, and How
The right-way guide to bearing replacement, and the warning signs you should never skip.
Read guideStop fixing the same fault twice.
Dovient turns guides like this into your team's shared playbook, with AI that catches recurring issues before they break the line.