TL;DR
Carryover means liquid water is leaving the tower with the exhaust air. Check fan speed against design, inspect drift eliminators for damage, and verify the circulating water flow rate is not above the design maximum.
What you might see
- wet surfaces and puddles downwind of the tower
- makeup water consumption above expected evaporation
- scale deposits on nearby structures
- visible water droplets exiting the fan stack
Likely causes
Excessive fan speed or airflow rate above the drift eliminator design velocity
Damaged or improperly seated drift eliminator panels allowing bypass
Overcirculation: water flow rate exceeding the tower design maximum
High wind conditions that defeat the eliminator at certain wind directions
Required tools
- Tachometer (contact or non-contact)
- LOTO kit
- Flow meter or pump curve data
Safety first
- Lock out the fan before inspecting drift eliminators inside the tower.
- Carry-over water contains concentrated cooling tower chemistry. Keep personnel out of the downwind zone during diagnosis.
Procedure
- 1
Measure the fan RPM with a tachometer and compare to the design value on the Marley nameplate. Reduce fan speed if above design.
- 2
Lock out the fan and inspect the drift eliminator panels for damage or gaps (see the excessive-drift procedure on this machine).[1]
- 3
Measure the circulating water flow rate and compare to the design GPM on the tower datasheet. Reduce flow if above design maximum.
- 4
Check that all distribution nozzles are oriented correctly and not spraying into the airstream above the fill.[1]
- 5
If high winds are the trigger, check whether a wind shield or louver panel is specified for this installation. Install if missing.
- 6
After corrections, observe the discharge plume from multiple angles in normal operating conditions. Droplets should not be visible more than 1 meter from the discharge.
Sources
Marley NC Cooling Tower User Manual, Marley Cooling (SPX Cooling Technologies)
Marley NC Cooling Tower Installation, Operation and Maintenance manual, drift and carryover troubleshooting (general)
View source
More guides for Marley (SPX Cooling) NC
How to eliminate algae and biofouling in a Marley NC cooling tower
Algae and biofilm grow when biocide levels drop below effective concentration. Perform a shock biocide dose, clean the basin, and review the ongoing chemical dosing schedule with your water treatment provider.
How to remove basin sediment buildup in a Marley NC cooling tower
Basin sediment accumulates when blowdown rate is too low or the side-stream filter is undersized or bypassed. Clean the basin, increase blowdown, and restore the filtration program.
How to fix excessive drift on a Marley NC cooling tower
Excessive drift means water droplets are escaping with the exhaust air. Inspect the drift eliminator sections for damage or missing panels and replace any that are cracked or displaced.
How to diagnose and fix fan vibration on a Marley NC cooling tower
Fan vibration is usually an imbalanced or damaged blade, inconsistent blade pitch angle, or worn gearbox bearings. Inspect blades, verify all pitch angles are equal, and check gearbox oil level and bearing condition.
Related learning guides
Stop fixing the same fault twice.
Dovient turns guides like this into your team's shared playbook, with AI that catches recurring issues before they break the line.