TL;DR
Basin sediment accumulates when blowdown rate is too low or the side-stream filter is undersized or bypassed. Clean the basin, increase blowdown, and restore the filtration program.
What you might see
- visible sludge or sand-like deposits in basin
- strainer clogging more frequently than normal
- turbid circulating water
- pump suction losing flow intermittently
Likely causes
Insufficient blowdown allowing suspended solids to concentrate and settle
Clogged or bypassed side-stream filtration not removing fine particles
Airborne dust and debris entering the open basin
Biological die-off and scale flakes from an inadequate treatment program
Required tools
- LOTO kit
- Basin vacuum or scoop
- Conductivity meter
- Replacement filter media or cartridges
- Hose for flushing
Safety first
- Basin sludge may contain biological hazards. Wear gloves and eye protection when removing sediment.
- Lock out the pump before reaching into the strainer or basin piping.
Procedure
- 1
Lock out the fan motor and circulating pump.
Warning: Confirm zero pressure on the pump discharge before opening any connections. - 2
Reduce basin water level to the minimum and manually remove settled sludge with a basin vacuum or scoop.
- 3
Flush the basin with clean water and remove loosened debris.
- 4
Inspect the pump suction strainer and clean it. Note what debris type dominates (scale, biological, airborne dirt) to guide root-cause correction.
- 5
Inspect the side-stream filter media or cartridge. Replace or backwash if saturated.[1]
- 6
Adjust the blowdown controller setpoint. Target conductivity per your water treatment provider's recommendation, typically 1500-2500 microsiemens/cm depending on makeup water quality.
- 7
Refill the basin and restore normal operation.
- 8
Re-inspect the basin after 7 days and compare sediment accumulation to baseline.
Sources
Marley NC Cooling Tower User Manual, Marley Cooling (SPX Cooling Technologies)
Marley NC Cooling Tower Installation, Operation and Maintenance manual, basin maintenance and filtration procedures (general)
View source
More guides for Marley (SPX Cooling) NC
How to eliminate algae and biofouling in a Marley NC cooling tower
Algae and biofilm grow when biocide levels drop below effective concentration. Perform a shock biocide dose, clean the basin, and review the ongoing chemical dosing schedule with your water treatment provider.
How to fix excessive drift on a Marley NC cooling tower
Excessive drift means water droplets are escaping with the exhaust air. Inspect the drift eliminator sections for damage or missing panels and replace any that are cracked or displaced.
How to diagnose and fix fan vibration on a Marley NC cooling tower
Fan vibration is usually an imbalanced or damaged blade, inconsistent blade pitch angle, or worn gearbox bearings. Inspect blades, verify all pitch angles are equal, and check gearbox oil level and bearing condition.
How to restore reduced cooling capacity on a Marley NC cooling tower
Reduced capacity is usually scaled fill blocking air-water contact, low water flow, or a fan running below design speed. Inspect fill, measure flow, and verify fan RPM.
Related learning guides
Lubrication Best Practices
The most overlooked maintenance task, and how to do it right.
Read guideShaft Alignment Fundamentals
Precision alignment that prevents bearing, seal, and coupling failures.
Read guideWhat is Root Cause Analysis (RCA)?
Find the real failure point so the same fault stops showing up every month.
Read guideStop fixing the same fault twice.
Dovient turns guides like this into your team's shared playbook, with AI that catches recurring issues before they break the line.