TL;DR
Reduced capacity is usually scaled fill blocking air-water contact, low water flow, or a fan running below design speed. Inspect fill, measure flow, and verify fan RPM.
What you might see
- leaving water temperature above design point
- condenser supply water warmer than normal
- reduced approach temperature to wet bulb
- process cooling inadequate under normal load
Likely causes
Scaled or fouled fill media blocking air-water contact surface
Low circulating water flow from a worn pump, throttled valve, or clogged strainer
Fan running below design speed from belt slip, worn sheaves, or motor underspeed
Clogged spray nozzles causing uneven water distribution over fill
Required tools
- Calibrated thermometer or thermocouple
- Wet-bulb thermometer or sling psychrometer
- Tachometer (contact or non-contact)
- LOTO kit
- Nozzle pick or small wire brush
- Flow meter or pump curve data
Safety first
- Lock out the fan motor before entering the tower plenum. Fan blades are not guarded inside the tower.
- Cooling tower basins may contain biological hazards including Legionella. Wear gloves and eye protection when working near basin water.
Procedure
- 1
Record the entering and leaving water temperatures and the ambient wet-bulb temperature. Compare them to the original tower design conditions.
- 2
Lock out the fan motor and circulating pump before any physical inspection.
Warning: Rotating fan blades cause severe injury. Lock out before entering the tower plenum. - 3
Inspect the fill media from above and below. Look for scale deposits, biological growth, or collapsed sections that restrict air flow.[1]
- 4
Measure the circulating water flow rate at the pump discharge. Compare to the design GPM on the Marley NC nameplate.
- 5
Check the inlet strainer on the pump suction for debris. Clean it if partially blocked.
- 6
Inspect each spray nozzle or distribution basin orifice for scale or debris. Clear blocked nozzles with a brush or nozzle pick.
- 7
Re-energize the fan and measure the fan RPM with a tachometer. Compare to the design RPM on the fan curve.
- 8
If fan speed is low, check belt tension and sheave wear. Adjust or replace belt as needed.[1]
- 9
If fill is heavily scaled, schedule a chemical descaling or fill replacement during the next planned shutdown.
Sources
Marley NC Cooling Tower User Manual, Marley Cooling (SPX Cooling Technologies)
Marley NC Cooling Tower Installation, Operation and Maintenance manual, performance and fill inspection procedures (general)
View source
More guides for Marley (SPX Cooling) NC
How to eliminate algae and biofouling in a Marley NC cooling tower
Algae and biofilm grow when biocide levels drop below effective concentration. Perform a shock biocide dose, clean the basin, and review the ongoing chemical dosing schedule with your water treatment provider.
How to remove basin sediment buildup in a Marley NC cooling tower
Basin sediment accumulates when blowdown rate is too low or the side-stream filter is undersized or bypassed. Clean the basin, increase blowdown, and restore the filtration program.
How to fix excessive drift on a Marley NC cooling tower
Excessive drift means water droplets are escaping with the exhaust air. Inspect the drift eliminator sections for damage or missing panels and replace any that are cracked or displaced.
How to diagnose and fix fan vibration on a Marley NC cooling tower
Fan vibration is usually an imbalanced or damaged blade, inconsistent blade pitch angle, or worn gearbox bearings. Inspect blades, verify all pitch angles are equal, and check gearbox oil level and bearing condition.
Related learning guides
What is Root Cause Analysis (RCA)?
Find the real failure point so the same fault stops showing up every month.
Read guideEquipment Breakdown Response
The step-by-step playbook for the first 15 minutes after a critical machine goes down.
Read guideHydraulic System Troubleshooting
Diagnose the most common hydraulic failures, fast.
Read guideStop fixing the same fault twice.
Dovient turns guides like this into your team's shared playbook, with AI that catches recurring issues before they break the line.