TL;DR
Battery high temperature accelerates capacity loss. Check the room HVAC, verify individual battery temperatures, and schedule an impedance test to identify weak cells.
What you might see
- battery high-temp alarm on display
- battery room ambient above 25 degrees C
- battery strings showing elevated impedance
- reduced runtime on battery test
Likely causes
HVAC failure in the battery room raising ambient above 25 degrees C
Battery thermal runaway in one or more weak cells
Blocked airflow between battery strings
Charger voltage set too high causing excess gassing and heat
Required tools
- IR thermometer
- Thermometer (ambient)
- UPS battery test kit or impedance tester
- Multimeter rated for battery bus voltage
- PPE: insulated gloves, face shield
Safety first
- UPS battery strings operate at hazardous DC voltage (typically 480 VDC on high-capacity strings). Use insulated tools and PPE at all times.
- Failing VRLA batteries can vent hydrogen gas. Ensure adequate ventilation and prohibit open flames or sparks near the battery room.
- Do not short battery terminals. Internal short can cause an explosion and fire.
Procedure
- 1
Acknowledge the alarm on the UPS display and record the timestamp.
- 2
Measure the battery room ambient temperature with a thermometer. The target is 20 to 25 degrees C for VRLA batteries.[1]
- 3
Check the battery room HVAC supply and return vents for blockage. Verify the unit is running.
- 4
Use an IR thermometer to scan each battery jar. Any cell more than 3 degrees C above the average string temperature is suspect.[1]
- 5
Measure the charger float voltage. Compare against the specification for the installed battery type and temperature.
- 6
If one or more cells are significantly hotter than the rest, isolate that string from the bus and schedule replacement.
- 7
If room temperature is normal and all cells are uniform, log the event and perform a scheduled impedance test within 30 days.
Sources
Eaton Eaton 9395 / 93PM UPS System (Industrial) general technical documentation, Eaton
Eaton 9395 / 93PM UPS general battery maintenance and temperature monitoring procedures (general)
More guides for Eaton Eaton 9395 / 93PM
How to fix inverter output voltage distortion on an Eaton 9395 / 93PM UPS
Output voltage distortion above 5 percent THD can reset sensitive pharma instrumentation. Check the output filter capacitors and inverter IGBT driver boards.
How to diagnose a static bypass failure on an Eaton 9395 / 93PM UPS
A static bypass fault means the SCR assembly or bypass synchronization has failed. The load is unprotected. Identify the root cause before transferring back to inverter.
Related learning guides
Stop fixing the same fault twice.
Dovient turns guides like this into your team's shared playbook, with AI that catches recurring issues before they break the line.