TL;DR
Repeated false stops in the same location usually mean a dirty safety scanner or a highly reflective surface (shrink wrap, chrome rack label) creating a phantom return. Clean the scanner and identify nearby reflectors.
What you might see
- robot stopping repeatedly in the same aisle location with no visible obstacle
- safety scanner fault alarm on the fleet console
- robot throughput declining due to excessive false stops
- safety scan zone event logged in the absence of any person or object in the path
Likely causes
Dirty safety laser scanner window scattering its own beam and registering a false detection
Highly reflective surfaces (shrink-wrapped pallets, mirror-finish racking) creating back-scatter detections inside the safety zone
Floor level debris (small cardboard pieces, stretch film) within the scan zone height triggering a stop
Safety zone configuration tuned too conservatively for the actual aisle dimensions
Required tools
- Fleet management console for event log and scan zone diagnostic
- Lint-free cloth for scanner window cleaning
Safety first
- Safety laser scanners are safety-critical devices. Do not adjust scan zone boundaries without a formal risk assessment and site safety approval.
- When performing any close-range inspection in an active AMR aisle, alert warehouse personnel and ensure the aisle is clear before working at floor level.
Procedure
- 1
Note the location and direction of the false stop from the fleet console log. If it always happens at the same location, a local environment factor is responsible.[1]
- 2
Inspect the safety scanner window on the robot at the reported stop location. Clean the window with a dry lint-free cloth.
Warning: Safety laser scanners are safety-rated devices. Do not modify scan zone configurations without completing a safety risk assessment and following the change-control procedure for your site. Reducing a safety zone boundary without authorization can endanger personnel. - 3
Walk the aisle at the false-stop location and look for highly reflective surfaces near floor level: silver pallet labels, chrome rack legs, or low-slung shrink wrap. Mask or reposition any identified reflector.
- 4
Inspect the floor in the false-stop area for small debris at scanner height. Clear any debris from the path.
- 5
Check the safety scanner diagnostic data from the fleet console to identify which scan zone segment triggered the stop. This narrows the physical search area.
- 6
If reflectors have been addressed and false stops continue, submit a scan zone review request to the system integrator or OEM, with the logged event data attached.
Sources
Locus Robotics Locus Origin AGV / AMR (Mobile Robots) general technical documentation, Locus Robotics
AMR safety scanner maintenance, false positive detection troubleshooting, general material handling references (general)
More guides for Locus Robotics Locus Origin
How to diagnose battery charging failure and short run time on a Locus Robotics Locus Origin AMR
Short run time or incomplete charge is almost always a dirty dock contact or a battery cell that has lost capacity. Clean the charging contacts first; if health flags persist, escalate to the OEM for battery replacement.
How to diagnose navigation path deviations on a Locus Robotics Locus Origin AMR
Navigation deviations are usually caused by a dirty LIDAR sensor, a damaged floor fiducial marker, or a stale map that does not match the current warehouse layout. Clean the LIDAR and verify map version first.
Related learning guides
Motor Troubleshooting: Symptoms to Fix
Read motor symptoms correctly and get to the root cause in minutes, not hours.
Read guideLubrication Best Practices
The most overlooked maintenance task, and how to do it right.
Read guideShaft Alignment Fundamentals
Precision alignment that prevents bearing, seal, and coupling failures.
Read guideStop fixing the same fault twice.
Dovient turns guides like this into your team's shared playbook, with AI that catches recurring issues before they break the line.