TL;DR
Overheating almost always means a blocked intercooler or aftercooler. Clean both coolers and verify the thermostatic bypass valve opens at the correct temperature.
What you might see
- high temperature shutdown fault on controller
- compressor trips on thermal protection
- outlet oil temperature above 100 degC
- hot air discharge from enclosure
Likely causes
Blocked intercooler or aftercooler fins reducing heat transfer, common in dusty environments
Thermostatic bypass valve stuck open, routing hot oil directly to the element without cooling
Low oil level reducing the cooling circuit's heat capacity
Ambient temperature above the compressor's rated maximum, insufficient ventilation in the compressor room
Required tools
- Coil fin cleaning brush or low-pressure air nozzle
- Non-conductive coil cleaner spray
- Thermometer (ambient)
- IR thermometer
- LOTO kit
- Atlas Copco-approved compressor oil
Safety first
- Depressurize and allow the compressor to cool before opening access panels. Hot oil and pressurized air are present.
- Use PPE when handling compressor oil. Some formulations are skin irritants.
Procedure
- 1
Read the fault history on the Elektronikon controller. Record the exact temperature and time of the high-temperature shutdown.[1]
- 2
Lock out the compressor and allow it to cool for 30 minutes before opening access panels.
- 3
Inspect the cooler fins. Clean both the intercooler and aftercooler with low-pressure compressed air or a non-conductive coil cleaner spray.[1]
- 4
Check the oil level in the sight glass. Top up with Atlas Copco-approved oil if below the min mark.
- 5
Verify room ambient temperature with a thermometer. If above 40 degC (or the rated limit on the nameplate), improve ventilation or add a room cooler.
- 6
Test the thermostatic valve by observing oil temperature on the controller display during a supervised start. Oil temperature should begin dropping once the thermostat opens, typically around 70 degC.
- 7
If the thermostat does not open and temperature climbs unchecked, replace the thermostatic cartridge.
Sources
Atlas Copco GA VSD+ Air Compressor User Manual, Atlas Copco
Atlas Copco GA VSD+ IOM, cooling system maintenance and thermostatic valve procedures (general)
View source
More guides for Atlas Copco GA VSD+
How to find and fix air leaks on an Atlas Copco GA VSD+ compressor installation
Walk the system with a sonic leak detector at every joint, fitting, and drain. Prioritize leaks by flow rate. A 3 mm orifice leak at 7 bar wastes roughly 60 SCFM continuously.
How to fix excessive vibration on an Atlas Copco GA VSD+ air compressor
Excessive vibration is most often loose foundation bolts or collapsed anti-vibration mounts. Torque the foundation bolts first, then check the mounts before suspecting the airend.
How to fix low pressure output on an Atlas Copco GA VSD+ air compressor
Low pressure output is most often worn inlet valve plates allowing blow-by. Check separator delta-P first, then do a compression efficiency test.
How to fix oil carryover in the discharge air on an Atlas Copco GA VSD+
Oil in discharge air means the separator element is saturated or the scavenge orifice is blocked. Replace the separator element and clear the scavenge line.
Related learning guides
Bearing Replacement: When, Why, and How
The right-way guide to bearing replacement, and the warning signs you should never skip.
Read guidePump Failure: 8 Common Causes
The most frequent pump failure modes and how to prevent them.
Read guideMotor Troubleshooting: Symptoms to Fix
Read motor symptoms correctly and get to the root cause in minutes, not hours.
Read guideStop fixing the same fault twice.
Dovient turns guides like this into your team's shared playbook, with AI that catches recurring issues before they break the line.